From TechnoDocs
Jump to: navigation, search

Inverter Settings for Motortronics or Teco inverters

For Spindles up to 10HP

The following settings must be set. All others should be left set to the factory defaults as indicated in the inverter manual.

Press “Display Func”

You get F000 – this means “Function 0”

Increment using the arrow keys to the appropriate value. Press Enter

Using the up, down, and left/reset arrows, set the value. Press Enter

Repeat for each necessary function

1: 0.9

2: 0.9

3: 0100

5: 18

6: 300 see note 1.

7: 100 see note 2.

10: 1 - start/stop from program.

11: 1 - speed set from potentiometer or ATC speed control

12: 1

17: 100.0

18: 133.0

19: 166.0

20: 200.0 Functions 17 through 23 are for TOOLCHANGER machines only

21: 233.0

22: 266.0

23: 300.0

25: set same as function 6

37: set same as function 6

70: set to motor rated current on motor nameplate for appropriate voltage


note 1: Function 6 is the maximum output frequency this should be set to the maximum rated frequency of the spindle. This is normally 300 for 18,000 RPM spindles or 400 for 24,000 RPM spindles. Consult spindle documentation and motor nameplate for maximum frequency.

note 2: Function 7 is the lower output frequency limit. The minimum for 18,000 RPM and 24,000 RPM spindles is 100 which corresponds to 6000 rpm. Operating at speeds below this may cause motor overheating and damage to the motor. Consult spindle documentation and motor nameplate for lower frequency rating.

note 3: For analog speed control on riser card

Function 11 = 2 Function 26 = 98 Function 28 is approximately 84, plus/minus 2 depending on the computer. (lower #28 makes top speed faster)




MA 7200 Inverter:

BN1 0.9 acc BN2 0.9 dec

CN2 300 Max Freq CN4 300 Full voltage freq CN9 Current from motor name plate

SN2 15 V/F profile SN3 7 Operator initialization

SN4 1 Control term run source set to 0 for keypad 1 for remote SN5 0 frequency source keypad SN8 1 Reverse inhibit SN67 0 V/F mode SN25 2 in term 5 2 wire control